SEW變頻器MOVITRAC-31C系列故障代碼表

發布時間:2019-08-02 15:42:24來源:

故障代碼 故障現象/類型 故障原因 解決對策
1 Overcurrent Short circuit/earth fault at the output. Motor too large. Faulty output stage. Remove short-circuit. Connect smaller motor. If fault can still not be reset, contact SEW service.
2 DC link voltage DC link voltage too high. Increase deceleration ramps.
3 Brake chopper Regenerative power too high Braking resistor circuit interrupted Short-circuit in the braking resistor circuit Braking resistance value too high Faulty brake chopper Increase deceleration ramps. Check connecting leads of the braking resistor. Check technical data of the braking resistor. Exchange MOVITRAC® 31C
5 Regenerative overload With active regen. n monit. (P520/P522) and speed control (P770): faulty encoder signals wrong number of pole pairs (P324/P344) value of increments (P773) not correct Check encoder. Check encoder connection. Set number of pole pairs correctly. Set value of increments correctly.
4 Cont. overload ´t utilization too high (> 125(%)). Reduce load.
6 Overtemperature Thermal overload of the inverter. Reduce load and / or ensure adequate cooling.
7 Phase failure With active mains volt. monitor.(P530) Phase missing at TL. X1:1/2/3. Check mains supply.
10 Direction of rotation Only with active speed control (P770): Encoder tracks A/A and B/B are swapped in pairs. Motor rotates in opposite direction. Regen. overload (i.e. with sagging hoist) because of excessive load or BOOST setting too low (P321/P341). Check encoder connection. Exchanging two motor phases. Reduce load or increase BOOST.
11 Speed detection Only with active speed control (P770): Faulty encoder connection. FEN31C/FPI31C option not installed. Check encoder connection. Insert correct option (FEN31C or FPI31C).
12 Mot. overload With active n monit. (P510/P512) and speed control (P770): faulty encoder signals wrong number of pole pairs (P324/P344) value of increments (P773) not correct Check encoder. Check encoder connection. Set number of pole pairs correctly. Set value of increments correctly.
13 Starting conditions With active hoist function (P710/P712): Current too low during the premagnetization phase: Motor rated power selected too small in relation to the inverter rated power. Cross-section of the motor leads too small. Check startup data and carry out new startup if necessary. Check inverter-motor connection. Check cross-section of the motor leads and increase if necessary.
14 Output open With active hoist function (P710/P712): Two or all output phases interrupted. Motor rated power selected too small in relation to the inverter rated power. Check inverter-motor connection. Check startup data and carry out new startup if necessary.
17 Stack overflow Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
18 Stack underflow Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
19 NMI trap Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
20 Undefined opcode Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
21 Protected instr. Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
22 Word op. access Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
23 nstruct. access Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly,
24 Ext. bus access Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.

故障代碼 故障現象/類型 故障原因 解決對策
25 EEPROM Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
26 No connection Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
27 Ext. terminal External fault signal has appeared at a programmable input Eliminate the cause of the fault. Reprogram the terminal, if necessary
28 Fault INTERBUS FFI31C and control mode (P841) = Fieldbus: Faulty monitoring signal. Check Fieldbus connection.
32 Copying Only when copying the parameters (P820): Break or interference in PC or FBG31C connection. Check connection between inverter and PC. Remove FBG31C keypad and plug again.
33 Master-slave Connection master-slave is interrupted. 0V5 connection (RS-485) missing Master or slave defined incorrectly in P880. Check master-slave connection. 0V5-establish connection between master and slave Set P880 correctly.
34 Fieldbus timeout No communication between master and slave within the specified time of the response monitoring. Check communication routine of the master. Increase fieldbus timeout time (P571)/ deactivate monitoring.
35 Connection Encoder-FRS Encoder connection faulty. Power supply of the encoder faulty. Check encoder connection. Check power supply of the encoder.
36 Connection Master-slave Only with FRS and cable break master-slave (P557) = YES: Setpoint connection of slave (TL. 98-101) is disrupted. Master Speed 0 ® slave FRS CTRL is disrupted. Slave FRS CTRL input not assigned. Master Speed 0 output not assigned. No master inverter available. Encoder < 512 pulses per revolution used. Check installation. Check programming of the binary inputs and binary outputs. Check if encoder type is correct.
37 FRS RAM fault Internal fault. If fault occurs repeatedly, contact SEW service.
38 FRS process data fault Fault on interface between inverter and FRS. If fault occurs repeatedly, contact SEW service.
39 FRS parameter data fault Invalid value for FRS parameters (P55_). Check parameter settings.
41 FRS lag fault Polarity of the encoder not set correctly. Acceleration ramps too short. P-gain of the positioning controller too small Speed controller not set property. Value for lag error tolerance too small Change polarity of encoder. Increase ramps. Increase P-gain. Select new parameters for speed controller. Increase lag error tolerance (P551). Check wiring of encoder, motor and mains phases. Check if mechanical system is sluggish or whether drive hit an obstacle.
43 Fault binary output Load on TL. X3:61 > 150 mA. Load on the other binary outputs > 50 mA Short circuit on binary output. Capacitive load on binary output. Check installation of the binary outputs.

、、、、、、、長治變頻器維修、、、、信陽變頻器維修、、、,河南鄭州變頻器專業銷售維修中心,技術精湛,質量可靠,價格比較低,信譽保證!變頻器維修電話:15515598858 0371-56700815

用手機看
SEW變頻器MOVITRAC-31C系列故障代碼表

拍下二維碼,信息隨身看

試試用手機掃一掃,
在你手機上繼續觀看此頁面。

主站蜘蛛池模板: 91精品综合久久久久m3u8 | 日韩一区二区视频 | 天堂一区| 国产精品久久一区一区 | 99re国产精品视频首页 | 欧美色视频日本片高清在线观看 | 女人18特级一级毛片免费视频 | 一级啪啪片 | 欧美日韩性视频在线 | 国产成年人视频 | 天天操天天射天天爽 | 久久综合婷婷 | 羞羞视频网站 | 久久99热久久精品91 | 一级黄网| 久草视频在线网 | 久久精品中文字幕久久 | 日韩欧美在线观看视频一区二区 | 色综合天天综合给合国产 | 青草久草 | 精彩视频一区二区三区 | 中文字幕视频在线观看 | 精品中文字幕一区二区三区四区 | 国产又黄又a又潮娇喘视频 国产又色又爽又黄又刺激18 | 国产在线精品成人一区二区三区 | 91精品在线免费 | 欧美性xxx免费看片 欧美性白人顶级hd 欧美性插视频 | 国产精品国产三级国产an | 久久亚洲视频 | 中文精品北条麻妃中文 | 亚洲女人天堂a在线播放 | 91色国产在线 | 91久久亚洲国产成人精品性色 | 久久五月天婷婷 | 国产黄色一级大片 | 亚洲精品乱码久久久久久v 亚洲精品乱码久久久久久麻豆 | 神马影院在线观看我不卡 | 欧美做爰xxxⅹ性欧 欧美做爰xxxⅹ在线视频hd | 欧美日韩国产成人综合在线 | 国产激情视频在线观看首页 | 久久99精品国产免费观看 |