SEW變頻器MOVITRAC-07系列故障代碼詳表

發(fā)布時間:2019-08-02 15:40:24來源:

故障代碼 故障現(xiàn)象/類型 故障原因 解決對策
01 Over-current • Short circuit on output • Output switching • Motor too large • Defective output stage • Ramp limit (P138) switched off • Rectify the short circuit • Only switch when output stage inhibited • Connect a smaller motor • Call SEW Service for advice if the fault still cannot be reset • Ramp limit (P138 = YES)
03 Ground fault • Ground fault on motor • Ground fault on inverter • Ground fault in the motor lead • Over-current (see F-01) • Replace the motor • Replace the MOVITRAC® 07 • Rectify the ground fault • See F-01
04 Brake chopper • Regenerative power excessive • Braking resistor circuit interrupted • Short circuit in braking resistor circuit • Excessively high braking resistance • Brake chopper defective • Ground fault • Extend deceleration ramps • Check connecting harness for braking resistor • Rectify the short circuit • Check technical data of braking resistor • Replace the MOVITRAC® 07 • Rectify the ground fault
06 Supply system phase failure (only with three-phase inverter) Phase fault Check supply system lead
07 DC-link overvoltage • DC link voltage too high • Ground fault • Extend deceleration ramps • Check connecting harness for braking resistor • Check technical data of braking resistor • Rectify the ground fault
08 Speed monitoring Current controller is operating at the setting limit due to: • mechanical overload • phase failure in supply system • phase failure in motor • Reduce load • Increase delay time setting P501 • Check current limitation • Extend deceleration ramps • Check supply system phases • Check motor feeder and motor Maximum speed for VFC operating mode exceeded • Reduce load • Increase delay time setting P501 • Check current limitation • Extend deceleration ramps • Check supply system phases • Check motor feeder and motor Maximum speed for VFC operating mode exceeded • Reduce maximum speed
10 ILLOP • Incorrect command during running of program • Incorrect conditions during running of program • Function not in inverter / not implemented • Check program • Check program structure • Use another function
11 Overtemperature Thermal overload of inverter • Reduce load and/or ensure adequate cooling • If the braking resistor is integrated in the heat sink: Mount the braking resistor externally
17-24 System fault Inverter electronics disrupted, possibly due to effect of EMC Check ground connections and shields; improve them if necessary. Contact SEW Service for advice if this reoccurs.
25 EEPROM Fault when accessing EEPROM Call up default setting, perform reset and set parameters again. Contact SEW Service for advice if this reoccurs.
26 External terminal Read in external fault signal via programmable input Eliminate specific cause of fault; reprogram terminal if appropriate.
31 TF sensor • Motor too hot, TF sensor has tripped • TF sensor of motor not connected or not connected properly • Connection of MOVITRAC® 07 and TF interrupted on motor • Let motor cool down and reset fault • Check connections/links between MOVITRAC® 07 and TF
32 Index overrun Basic programming rules violated causing internal stack overflow Check and correct user program
34 Ramp timeout The inverter signals F34 if you revoke the enable and the drive exceeds the rapid stop ramp time t13 by a certain time. Extend the rapid stop ramp time
37 Watchdog timer Fault in system software sequence Check ground connections and shields; improve them if necessary. Contact SEW Service for advice if this reoccurs.
38 System software System fault Check ground connections and shields; improve them if necessary. Contact SEW Service for advice if this reoccurs.
43 RS-485 timeout Communication between inverter and PC interrupted Check connection between inverter and PC.
44 Unit utilization Unit utilization (Ixt value) excessive • Reduce power output • Extend ramps • If these points are not possible: Use a larger inverter
45 Initialization Error during initialization Contact SEW Service for advice.
47 System bus timeout Fault during communication via system bus Check system bus connection.

故障代碼 故障現(xiàn)象/類型 故障原因 解決對策
77 Control word An external control has attempted to set an invalid automatic mode • Check serial connection to external control • Check write values of external control
81 Start condition Only in "VFC hoist" operating mode: The inverter could not inject the required amount of current into the motor during the pre-magnetization time: • Motor rated power too small in relation to inverter rated power • Motor cable cross section too small • Check connection between inverter and motor • Check startup data and repeat startup if necessary
82 Output open Only in "VFC hoist" operating mode: • Two or all output phases interrupted • Motor rated power too small in relation to inverter rated power Check connection between inverter and PC.
94 EEPROM checksum EEPROM defective Contact SEW Service for advice.
97 Copy fault • Parameter module disconnected during copying process • Switching off/on during copying process Prior to acknowledging the fault: • Load the factory setting or the complete data record from the parameter module
、、、、、、、長治變頻器維修、、、、信陽變頻器維修、、、,河南鄭州變頻器專業(yè)銷售維修中心,技術(shù)精湛,質(zhì)量可靠,價格比較低,信譽保證!變頻器維修電話:15515598858 0371-56700815
用手機看
SEW變頻器MOVITRAC-07系列故障代碼詳表

拍下二維碼,信息隨身看

試試用手機掃一掃,
在你手機上繼續(xù)觀看此頁面。

主站蜘蛛池模板: 免费毛片观看 | 欧美日本高清视频在线观看 | 亚洲欧美日韩激情在线观看 | 91成人在线免费视频 | 国产精品国产三级国产普通话 | 国产第一区二区三区在线观看 | 四虎影院在线播放 | 久久性生活片 | 国产香蕉在线视频 | 色费女人18毛片a级视频在线 | 亚洲国产第一区二区香蕉 | 日韩欧美~中文字幕 | 一级免费a | 国产精品一久久香蕉产线看 | 国产欧美日韩精品一区二 | 国产精品欧美一区二区 | 露脸真实国产精品自在 | 亚洲精品一区二区三区中文字幕 | 九九久久国产 | 女人18毛片一级毛片在线 | 精品国产一区二区三区香蕉沈先生 | 亚洲国产精久久小蝌蚪 | 久久综合九色综合97婷婷群聊 | 青青青手机视频 | 奇米影视77777 | 四虎国产在线 | 久久久综合九色合综国产 | 久久这里只精品国产99热 | 四虎在线免费观看 | 欧美日韩在线看 | 欧美毛片网 | 九九久久久2| 网曝门精品国产事件在线观看 | www日日日| 欧美亚洲国产成人高清在线 | 美女视频很黄很黄又免费的 | 欧美色黄毛片 | 天天插天天射天天干 | 夜色私人影院永久入口 | 国产视频一区二区在线播放 | 天天曰天天 |